             Technical Data 
            Features   
             | 
        
        
            | 
             Control Types 
             | 
            
             Full PID with Pre-tune, Self-tune,   manual tuning, or On-Off control. Heat only or heat & cool 
             | 
        
        
            | 
             Auto/Manual 
             | 
            
             Selectable from front panel or via   digital input, with bumpless transfer 
             | 
        
        
            | 
             Output Configuration 
             | 
            
             Up to 3 possible, for control, alarm, 24VDC   transmitter power supply or retransmit of process value or setpoint 
             | 
        
        
            | 
             Alarm 1 & 2 Types 
             | 
            
             Process high, process low, SP   deviation, band, logical OR / AND. Also 1 loop alarm for process control   security. Process alarms have adjustable hysteresis. 
             | 
        
        
            | 
             Human Interface 
             | 
            
             4 button operation, dual 4 digit 13mm   & 10mm high LED displays, optional choice of colours (Red/Red, Red/Green,   Green/Red or Green/Green), plus 5 LED indicators 
             | 
        
        
            | 
             PC Configuration 
             | 
            
             Off-line configuration from PC serial   port to dedicated config socket (comms option not required). Configuration   Software for Windows 98 or higher. West Part Number: PS1-CON 
             | 
        
        
            | 
             Input 
             | 
        
        
            | 
             Thermocouple 
             | 
            
             J, K, C, R, S, T, B, L, N &   PtRh20%vsPtRh40%. 
             | 
        
        
            | 
             RTD 
             | 
            
             3 Wire PT100, 50Ω per lead maximum   (balanced) 
             | 
        
        
            | 
             DC Linear 
             | 
            
             0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to   50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V. 
            Scaleable  -1999 to 9999, with adjustable decimal   point 
             | 
        
        
            | 
             Impedance 
             | 
            
             >10MΩ for Thermocouple and mV   ranges, 47KΩ for V ranges and 5Ω for mA ranges 
             | 
        
        
            | 
             Accuracy 
             | 
            
             ±0.1% of input range ±1 LSD (T/C CJC   better than 1°C) 
             | 
        
        
            | 
             Sampling 
             | 
            
             4 per second, 14 bit resolution   approximately 
             | 
        
        
            | 
             Sensor Break Detection 
             | 
            
             <2 seconds (except zero based DC   ranges), control O/P’s turn off, high alarms activate for T/C and mV ranges,   low alarms activate for RTD, mA or V ranges 
             | 
        
        
            | 
             Outputs & Options 
             | 
        
        
            | 
             Control & Alarm Relays 
             | 
            
             Contacts SPDT 2 Amp resistive at 240V   AC, >500,000 operations 
             | 
        
        
            | 
             Control SSR Driver Outputs 
             | 
            
             Drive capability >10V DC in 500Ω   minimum 
             | 
        
        
            | 
             Triac Outputs 
             | 
            
             0.01 to 1 Amp AC, 20 to 280Vrms, 47 to   63Hz 
             | 
        
        
            | 
             DC Linear Outputs 
             | 
            
             0 to 20mA, 4 to 20mA into 500Ω max, 0   to 10V, 2 to 10V, 0 to 5V into 500Ω min. 
            Control outputs have 2% over/under   drive applied. Accuracy ±0.25% at 250Ω (degrades linearly to 0.5% for   increasing burden to specified limits) 
             | 
        
        
            | 
             Transmitter Power Supply 
             | 
            
             Output 24VDC (nominal) into 910Ω   minimum to power external devices 
             | 
        
        
            | 
             Communications 
             | 
            
             2 Wire RS485, 1200 to 19200 Baud,   Modbus and ASCII protocol (selectable) 
             | 
        
        
            | 
             Digital Input 
             | 
            
             Selects between 2 setpoints or   Auto/Manual control. Volt free or TTL input 
             | 
        
        
            | 
             Remote Setpoint Input 
             | 
            
             0 to 20mA, 4 to 20mA, 0 to 5V, 1 to 5V,   0 to 10V or 2 to 10V.Scaleable -1999 to 9999. Local/Remote setpoint selected   from digital input (supplied as part of Full RSP) or front panel 
             | 
        
        
            | 
             Operating & Environmental 
             | 
        
        
            | 
             Temperature & RH 
             | 
            
             0 to 55°C (-20 to 80°C storage), 20% to   95% RH non-condensing 
             | 
        
        
            | 
             Power Supply 
             | 
            
             100 to 240V 50/60Hz 7.5VA (optional 20   to 48V AC 7.5VA/22 to 65V DC 5 watts) 
             | 
        
        
            | 
             Front Panel Protection 
             | 
            
             IEC IP66 (Behind panel protection is   IP20) 
             | 
        
        
            | 
             Standards 
             | 
            
             CE, UL & ULC recognised 
             |