| Parameter | Description | Type | Adjustment range | Factory Setting | User Setting | 
        
            | 1.01 | Read   speed reference before limits | RO | ± 1000.0 Hz 
 ±   30000 min-1 | - | - | 
        
            | 1.02 | Read speed reference before frequency   skips | RO | ± 1000.0 Hz 
   ± 30000 min-1 | - | - | 
        
            | 1.03 | Read speed reference before ramp | RO | ± 1000.0 Hz 
   ± 30000 min-1 | - | - | 
        
            | 1.04 | Speed reference offset | R/W | ± 1000.0 Hz 
   ± 30000 min-1 | Hz   0 min-1 |   | 
        
            | 1.05 | Jog reference | R/W | 0 to 400.0 Hz   0           to 4000 min-1 | 1.5 Hz   50 min-1 |   | 
        
            | 1.06 | Maximum speed or frequency limit | R/W | 0 to 1000.0 Hz   0 to 30000 min-1 |   1500 min-1   3000 min-1 |   | 
        
            | 1.07 | Maximum speed or frequency limit | R/W | 0 to 1.06 | Hz   0 min-1 |   | 
        
            | 1.08 | Selection of a negative minimum speed | R/W | 0 or 1 | 0 |   | 
        
            | 1.09 | Selection of speed reference offset | R/W | 0 or 1 | 0 |   | 
        
            | 1.10 | Selection of of bi-directional mode | R/W | 0 or 1 | 0 |   | 
        
            | 1.11 | Start command indicator | R/W | 0 or 1 | - | - | 
        
            | 1.12 | Direction of rotation indicator | RO | 0 or 1 | - | - | 
        
            | 1.13 | Jog operation indicator | RO | 0 or 1 | - | - | 
        
            | 1.14 | Selection of speed references | R/W | 0 or 5 | 0 |   | 
        
            | 1.15 | Selection of preset speeds | R/W | 0 or 9 | 0 |   | 
        
            | 1.16 | Preset speeds cycle time | R/W | 0 to 400.0s | 10.0s |   | 
        
            | 1.17 | Reference via keyboard | R/W | 1.07 to 1.06 | 0.0 Hz   0 min-1 |   | 
        
            | 1.18 | Precision reference (integer) | R/W | ± 1000.0 Hz ± 30000 min-1 | 0.0 Hz   0 min-1 |   | 
        
            | 1.19 | Precision reference (decimal) | R/W | 0 to 0.99 Hz   0 to 0.99 min-1 | 0.000Hz   0.00 min-1 |   | 
        
            | 1.20 | Precision reference enable | R/W | 0 or 1 | 0 |   | 
        
            | 1.21 To 1.28 | Preset speed 1  To Preset speed 8 | R/W | ± 1000.0 Hz   ± 30000 min-1 | 0.0 Hz   0 min-1 |   | 
        
            | 1.29 | Skip speed 1 | R/W | 0 to    1000.0 Hz   0 to 30000 min-1 | 0.0Hz   0 min-1 |   | 
        
            | 1.30 | Width of skip speed 1 | R/W | 0 to 50 Hz   0           to 50 min-1 | 0.5Hz   5 min-1 |   | 
        
            | 1.31 | Skip speed 2 | R/W | 0 to 1000.0 Hz   0 to 30000 min-1 | 0.0     Hz   0 min-1 |   | 
        
            | 1.32 | Width of Skip speed 2 | R/W | 0 to 50 Hz   0 to 50 min-1 | 0.5Hz   5 min-1 |   | 
        
            | 1.33 | Skip speed 3 | R/W | 0 to 1000.0 Hz   0 to 30000 min-1 | 0.5Hz   5 min-1 |   | 
        
            | 1.34 | Width of Skip speed 3 | R/W | 0 to 50 Hz   0 to 50 min-1 | - |   | 
        
            | 1.35 | Skip speed zone indicator | RO | 0 or 1 | - |   | 
        
            | 1.36 | Analogue speed reference 1 | R/A | ± 1.06 or  -1.07 to +1.06 | - |   | 
        
            | 1.37 | Analogue speed reference 2 | R/A | ± 1.06 or  -1.07 to +1.06 | - |   | 
        
            | 1.38 | Speed reference  adjustment | R/A | ± 100.0 % | - |   | 
        
            | 1.39 | Speed reference from synchro mode | RO | ± 1000.0 Hz   ± 30000 min-1 | - | - | 
        
            | 1.40 | Selection of speed reference from   synchro mode | RO | 0 or 1 | - |   | 
        
            | 1.41 To 1.47 | Selection of reference via logic inputs    | R/A | 0 or 1 |   - |   | 
        
            | 1.48 | Preset speed cycle reset | R/W | 0 or 1 | 0 |   | 
        
            | 1.49 | Selected reference indicator | RO | 1 to 5 | - |   | 
        
            | 1.50 | Selected preset speed indicator | RO | 1 to 8 |   |   |