Technical Data
Features
|
Control Types
|
Full PID with Pre-tune, Self-tune, manual tuning, or On-Off control. Heat only or heat & cool
|
Auto/Manual
|
Selectable from front panel or via digital input, with bumpless transfer
|
Output Configuration
|
Up to 3 possible, for control, alarm, 24VDC transmitter power supply or retransmit of process value or setpoint
|
Alarm 1 & 2 Types
|
Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process control security. Process alarms have adjustable hysteresis.
|
Human Interface
|
4 button operation, dual 4 digit 13mm & 10mm high LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED indicators
|
PC Configuration
|
Off-line configuration from PC serial port to dedicated config socket (comms option not required). Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
|
Input
|
Thermocouple
|
J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%.
|
RTD
|
3 Wire PT100, 50Ω per lead maximum (balanced)
|
DC Linear
|
0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Scaleable -1999 to 9999, with adjustable decimal point
|
Impedance
|
>10MΩ for Thermocouple and mV ranges, 47KΩ for V ranges and 5Ω for mA ranges
|
Accuracy
|
±0.1% of input range ±1 LSD (T/C CJC better than 1°C)
|
Sampling
|
4 per second, 14 bit resolution approximately
|
Sensor Break Detection
|
<2 seconds (except zero based DC ranges), control O/P’s turn off, high alarms activate for T/C and mV ranges, low alarms activate for RTD, mA or V ranges
|
Outputs & Options
|
Control & Alarm Relays
|
Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations
|
Control SSR Driver Outputs
|
Drive capability >10V DC in 500Ω minimum
|
Triac Outputs
|
0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz
|
DC Linear Outputs
|
0 to 20mA, 4 to 20mA into 500Ω max, 0 to 10V, 2 to 10V, 0 to 5V into 500Ω min.
Control outputs have 2% over/under drive applied. Accuracy ±0.25% at 250Ω (degrades linearly to 0.5% for increasing burden to specified limits)
|
Transmitter Power Supply
|
Output 24VDC (nominal) into 910Ω minimum to power external devices
|
Communications
|
2 Wire RS485, 1200 to 19200 Baud, Modbus and ASCII protocol (selectable)
|
Digital Input
|
Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input
|
Remote Setpoint Input
|
0 to 20mA, 4 to 20mA, 0 to 5V, 1 to 5V, 0 to 10V or 2 to 10V.Scaleable -1999 to 9999. Local/Remote setpoint selected from digital input (supplied as part of Full RSP) or front panel
|
Operating & Environmental
|
Temperature & RH
|
0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
|
Power Supply
|
100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
|
Front Panel Protection
|
IEC IP66 (Behind panel protection is IP20)
|
Standards
|
CE, UL & ULC recognised
|