♦ Intrinsically safe sensor circuit
♦ 2 amps @ 230 VAC
♦ Switch status indication
♦ Wire Break Monitoring
♦ Use with all switches
♦ Reversible switch action
Technical Data
|
|
Power Supply Req’d (terminals 14 & 15) Input voltage Power consumption
|
Model KR120 - 120VAC 47-66Hz Model KR230 - 230VAC 47-66Hz Approx. 1.3W
|
Inputs (terminal 1+, 3-; 4+, 5-) Intrinsically safe (from KSR switch) Open circuit voltage UAO Short circuit current IAK Switch point within range IH Switching hysteresis IH Wire break
|
Approx. 8 VDC Approx. 8mA 1.2mA to 2.1mA Approx. .2mA Break at <0.1mA, short circuit >6mA
|
Output s (terminals 7, 8, 9, 10, 11, & 12) Contact Rating AC Contact Rating DC Change over time
|
Not intrinsically safe, 1 SPDT relay, potential free. 253VAC / 2Amp 30VDC / 2A / resistive load Approx. 20mS
|
Galvanic Isolation
|
Yes
|
Environmental Conditions
|
-20ºF to + 122ºF (-20C to + 50C)
|
Dimensions
|
2.36"W X 3.64H X 4.53"D (60mmW X 92.5mmH X 115mm D)
|
Housing Protection Class
|
IP 20 (Indoor Dry Locations)
|
Mounting Style
|
35mm DIN or Integral Screw Mounting Tabs Standard
|